Façade Statics: Wind Loads, Deflection and Vertical Mullion Selection

Sample Façade Structural Report

Below is a sample façade statics report prepared by façade consultant and civil engineer Utku Çiçek. The report includes wind load, deflection limits and required second moment of area (Ireq) in line with TS 498 and EN 1991-1-4. It can be used for profile selection, engineering verification and safety checks in unitized/curtain walls and aluminum façade systems.

PDF
View Sample Report

We also provide anchor, bolt and welded connection checks as well as continuous beam and other structural analyses.

Vertical Mullion Analysis [ under wind load ]

Enter the design area load (kN/m²). Multiplying by the module/axis width B yields the line load w (kN/m). With the span L (cm), the EN 13830:2015+A1:2020 deflection limit is auto-selected and the required second moment of area (Ireq) is obtained from the simply supported beam formula (two pinned supports).

R R Distributed Wind Load L

Inputs

Note: w = |q| × B (kN/m). Deflection limit per EN 13830 5.7–5.8: L ≤ 3000 mm → L/200; 3000 < L < 7500 mm → 5 mm + L/300; L ≥ 7500 mm → L/250.

Results

Wind sign (input)
Line load w
kN/m
Deflection limit flimit
mm
Required Ireq
cm⁴
Max deflection Δmax
mm
R (SLS)
kN
Vmax (SLS)
kN
Mmax (SLS)
kN·m
Rd (ULS)
kN
Md (ULS)
kN·m
σd (ULS)
MPa

SLS (Deflection)

Δmax / flimit and Ireq

ULS (Stress)

σd / allowable and Md