1. Basic Wind Pressure Formula
w = Cp × q
where q is the velocity pressure (kN/m²) and
Cp the aerodynamic coefficient
(positive/negative).
2. Velocity Pressure (q)
q = v² / 1600 (TS 498 §14.3)
v = basic wind speed (m/s). Alternatively, design values may be taken directly from Table 4 of the standard.
3. Typical Cp Coefficients
-
Windward flat façade:
Cp ≈ +0.80(pressure) /–0.80(suction) -
Side façade (parallel flow):
Cp ≈ –0.50 - Corner zones / overhangs: safety factors may be increased.
4. Increase for Isolated Elements
For individual panels or frames the velocity pressure is increased by 25 %:
qdesign = 1.25 × q
5. Worked Example
- Height band: 21–100 m
- v = 42 m/s →
q = 1.10 kN/m²(tabulated) - Isolated panel:
q = 1.10 × 1.25 = 1.375 kN/m² -
Cp = 0.80(windward pressure) w = 0.80 × 1.375 ≈ 1.10 kN/m²
Beus Facade engineers combine TS 498 with TS EN 1991-1-4 to deliver façade designs compliant with both national and Eurocode requirements.