Türkçe English
Cephe Danışmanı - Facade Consultant Egemen Çalışkan WhatsApp Facade Consultant
Egemen Çalışkan
+90 541 239 92 27

TS EN 1991-1-4 – Wind Load Calculation

TS EN 1991-1-4 (Eurocode 1-4) defines façade wind actions in terms of building height, terrain roughness, orography and direction/season factors. The steps below show how to obtain the characteristic load for stick curtain-wall systems.

The procedure follows 7 core steps from the standard:

1. Basic Wind Velocity (Vb)

The map value Vb,0 is multiplied by direction (Cdir) and season (Cseason) factors:

Vb = Cdir × Cseason × Vb,0

2. Terrain Factor (Kr)

With roughness length z0:

Kr = 0.19 · (z0/0.05)0.07

3. Roughness Coefficient (Cr(z))

Obtained by multiplying Kr by ln(z / z0):

Cr(z) = Kr · ln(z / z0)

4. Mean Wind Velocity (Vm(z))

Vm(z) = Cr(z) × Co(z) × Vb

5. Turbulence Intensity (Iv(z))

Iv(z) = K1 / [Co(z) · ln(z / z0)]

6. Peak Velocity Pressure (qp(z))

qp(z) = 0.5 · ρ · Vm(z)2 · [1 + 7 · Iv(z)]

7. Net Surface Pressure (w)

w = qp(z) · (Cpe − Cpi)

In practice different Cpe values are taken for ZONE A (suction) and ZONE D (pressure). For sealed façades Cpi is commonly set to 0.

8. Recommended External Pressure Coefficients – Table 7.1

Table 7.1 of TS EN 1991-1-4 gives characteristic external pressure coefficients (Cpe,10 and Cpe,1) for vertical walls of rectangular-plan buildings. h/d is the ratio of building height to plan depth.

h/d Zone A Zone B Zone C Zone D Zone E
Cpe,10 Cpe,1 Cpe,10 Cpe,1 Cpe,10 Cpe,1 Cpe,10 Cpe,1 Cpe,10 Cpe,1
5 -1.2 -1.4 -0.8 -1.1 -0.5 -0.5 +0.8 +1.0 -0.7
1 -1.2 -1.4 -0.8 -1.1 -0.5 -0.5 +0.8 +1.0 -0.5
≤0.25 -1.2 -1.4 -0.8 -1.1 -0.5 -0.5 +0.7 +1.0 -0.3

Note — If wind force on both windward (Zone D) and leeward (Zone E) walls is applied simultaneously, correlation factors depending on h/d may be adopted: 1.00 for h/d ≥ 5, 0.85 for h/d ≤ 1; linear interpolation for intermediate ratios.

9. Cpe as a Function of Loaded Area

According to §7.2.1, use Cpe,1 for areas ≤ 1 m² and Cpe,10 for areas ≥ 10 m². For intermediate areas (1 m² < A < 10 m²) apply the logarithmic interpolation:

Cpe(A) = Cpe,1 − (Cpe,1 − Cpe,10) · log10(A)

A is the loaded area in m². The curve matches Cpe,1 at 1 m² and Cpe,10 at 10 m², decreasing linearly in log-space (see Figure 7.2).

Example — A = 3 m² panel

National Annexes may specify additional procedures or safety factors for areas > 10 m².

10. Numerical Verification

Beus Facade validates the resulting w values in FEM simulations, checking deflection limits, profile stresses and fixing safety.