Façade Statics: Glass Load, Deflection and Transom (Horizontal Mullion) Selection

Sample Façade Statics Report

Below is a sample façade statics report prepared by façade consultant and civil/structural engineer Utku Çiçek. The report covers glass self-weight, deflection limits, and the required second moment of area (Ireq) with references to TS 498, EN 1991-1-4, and EN 13830. It can be used for preliminary sizing, engineering verification, and structural safety checks of curtain wall and aluminum façade systems.

PDF
View Sample Report

Likewise, contact us for anchor, bolt, and welded connection checks, or for continuous beam and other structural analyses.

Transom (Horizontal Mullion) Calculation [ Based on glass self-weight ]

The glass panel weight is transferred to the transom via two hangers as concentrated loads P (symmetric double point loads). Given the support span L (cm), the distance from support a (cm), and the glass dimensions, per EN 13830:2015+A1:2020 the deflection limit f = L/500 is adopted; from this the Ireq and (optional) ULS stress check are calculated.

R R P P L a a
Glass weight carried by two hangers at the ends: symmetric double point loads (P).

Inputs

Notes: Wglass = 0.025 · ttotal · L · G (kN); P = Wglass/2. Deflection limit per EN 13830 Clause 5.6: f = L/500

Results

Total glass weight Wglass
kN
Point load P (each end)
kN
Maximum moment Mmax (SLS)
kN·m
Deflection limit flimit
mm
Required Ireq
cm⁴
Max deflection Δmax
mm
R (SLS)
kN
Rd (ULS)
kN
Md (ULS)
kN·m
σd (ULS)
MPa

SLS (Deflection)

Δmax / flimit and Ireq

ULS (Stress)

σd / allowable and Md